The results are generated with SDC Verifier 3.6 and calculated with FEMAP v11.0.0 Task: Determine the available shear strength and adequacy of L5×3×¼ (LLV) ASTM A36 with end shears of 3.50 kips from dead load and 10.5 kips from live load. Solution: From AISC Manual Table 2-4, the material properties are as follows: ASTM A36 Fy = 36 ksi Fu = 58 ksi From AISC […]
The results of tensile yielding and recommended slenderness limit calculation according to SDC Verifier and Design Examples of AISC (official version 14.1) are compared. The goal is to test SDC Verifier and reach valid results according to Specification for Structural Steel Buildings (ANSI/AISC 360-10 chapter D). The results are generated with SDC Verifier 3.6 and […]
The results of tensile yielding and recommended slenderness limit calculation according to SDC Verifier and Design Examples of AISC (official version 14.1) are compared. The goal is to test SDC Verifier and reach valid results according to Specification for Structural Steel Buildings (ANSI/AISC 360-10 chapter D). The results are generated with SDC Verifier 3.6 and […]
The results of tensile yielding and recommended slenderness limit calculation according to SDC Verifier and Design Examples of AISC (official version 14.1) are compared. The goal is to test SDC Verifier and reach valid results according to Specification for Structural Steel Buildings (ANSI/AISC 360-10 chapter D). The results are generated with SDC Verifier 3.6 and […]
The results of tensile yielding and recommended slenderness limit calculation according to SDC Verifier and Design Examples of AISC (official version 14.1) are compared. The goal is to test SDC Verifier and reach valid results according to Specification for Structural Steel Buildings (ANSI/AISC 360-10 chapter D).